Fire safety at Scout campsites

A Scout campsite needs a written fire risk assessment, and buildings where people sleep need the most from it: a proper fire alarm, fire doors that close, clear escape routes and a plan for getting everyone out at night. Campfire circles and fire pits belong in the assessment too.

This guide is for campsite managers, wardens and the Trustee Boards that run campsites. It applies to activity centres and Scout halls used for sleepovers as well. It’s a summary of Scouts’ guidance and the law, not legal advice: for anything beyond simple premises, get a competent fire risk assessor.

Who’s responsible

Fire safety law puts the duty on the responsible person: the employer, owner, landlord, occupier or whoever controls the premises. Scouts says that for most Scout premises that’s the Trustee Board, even if you don’t own the land. Where more than one body is responsible, such as a District site on a lease, each must cooperate with the others and agree who does what.

The law is the Regulatory Reform (Fire Safety) Order 2005 in England and Wales, the Fire (Scotland) Act 2005, and the Fire Safety Regulations (Northern Ireland) 2010.

The fire risk assessment

Buildings where people sleep

Scouts’ guidance sets extra requirements for premises built for or regularly used for sleeping, such as campsite lodges and bunkhouses. Your fire risk assessment decides the detail.

Every building

Getting everyone out

Campfire circles and fire pits

Scouts says fire pits, campfire circles and other open flames on your site belong in the fire risk assessment. Its suggested controls:

Visiting groups running their own campfire follow Scouts’ campfire safety guidance. Make your site’s rules part of the welcome briefing, including any fire ban in dry spells.

Regular checks

These are the usual intervals, from the British Standards and Scouts’ guidance. Your fire risk assessment may ask for more, or less for a simple building.

CheckHow oftenNotes
Fire alarm: test a call pointEvery weekA different call point each time, and log it
Smoke, heat and CO detectorsEvery weekPress to test
Emergency lighting: short testEvery monthFull-duration test once a year (BS 5266)
Fire extinguishers: visual checkEvery monthPresent, sealed, gauge in the green
Fire alarm: serviceEvery 6 monthsBy a competent person (BS 5839-1)
Fire doors: inspectionEvery 6 monthsClosers, seals, gaps, glass and signs
Evacuation drillAt least every 6 monthsIncluding a night-time plan where people sleep; keep a record
Fire extinguishers: serviceEvery yearBy a competent person (BS 5306-3)
Fire risk assessment: reviewRegularly, and after any change or incidentMost sites review it every year

Keep the record of every check. It’s the first thing a fire officer or an insurer asks to see.

Keep the checks and the record together

  • Campsite Manager has a standard list of compliance checks, built from Scouts’ Safe Scouting Premises Audit. Each check comes with a suggested interval and says where it comes from. The fire checks cover the weekly alarm test, emergency lighting, extinguishers, fire doors, drills and the fire risk assessment review.
  • Log each check as you do it, and say which buildings it covers. Some ask for a detail, such as the call point tested. A check that finds a problem stays due until a clear one is recorded, and whoever does it gets the reminder too. Compliance checks.
  • The evidence pack prints every check, its dates and any problems in one document, ready for an inspector or insurer.